Short Circuit Current & Fault Level Calculator

COMPUTE 3-PHASE SHORT CIRCUIT CURRENT (KA) & RECOMMENDED BREAKER ICU RATING

Short Circuit Fault Level Results

Nominal Transformer Current (A) --
Short Circuit at Transformer (kA) --
Short Circuit at Fault Point (kA) --
Recommended Breaker Icu (kA) --

Short Circuit Formulas

Isc = In / (%Z / 100) where In = S_trafo / (√3 × V_sec)

Electrical circuit breakers and switchgear must have a ultimate breaking capacity (Icu) higher than the maximum prospective short-circuit current to safely extinguish arcs during a fault.

Frequently Asked Questions

What is %Z (uk) impedance voltage of a transformer?

%Z (or uk) is the percentage of nominal primary voltage required to circulate nominal current through a short-circuited secondary winding. Standard distribution transformers (250kVA – 2500kVA) typically have uk values between 4% and 6%.

Why does short circuit current decrease over cable length?

Cables add electrical resistance (R) and reactance (X) to the fault loop impedance. Longer or thinner cables increase total loop impedance, reducing the fault current at the far end of the circuit.

What is the difference between Icu and Ics for circuit breakers?

Icu (Ultimate Breaking Capacity) is the maximum short-circuit current the breaker can interrupt twice without causing danger. Ics (Service Breaking Capacity) is the current it can interrupt three times and still remain fully operational without performance degradation.